The large (6-inch x 6-inch) PCB label is required as described below unless an item is too small (see 40 CFR 761.45). If an item is too small, you may use an identical small (2-inch x 2-inch) label.

PCB Marking Requirements

Item or Location

PCB Marking Required

PCB Container (50 ppm or greater)

Large PCB label

PCB Transformer (500 ppm or greater)

Large PCB label

PCB Large Capacitor (500 ppm or greater)

Large PCB label

PCB Article Container

Large PCB label

PCB Transformer enclosures (vault doors, machinery room doors, substation fence, hallway, etc.)

Large PCB label

PCB storage for disposal area (temporary and long term)

Large PCB label

Transport vehicle loaded with greater than 45 kg (99.4 lbs) of PCB liquids in PCB Containers, or one or more PCB Transformers

Large PCB label on front, back, and both sides of the trailer. (Note: A DOT Class 9 placard with ID number 2315 also may be required.  Check with your disposal company and shipper.)

Fluorescent light ballasts manufactured between July 1, 1979 and July 1, 1998

Manufacturers were required to mark with the statement “No PCBs.”